To Set Up the 935B Timer…
1. Plan a timer strategy.
2. Wire the Output 2 control output, associated
switching devices and annunciators. See p. 44-45.
3. Go to the 935B’s Configuration Menu [CnFG].
4. Choose the Output 2 [`Ot2] function as time;
hrs:min [thM], or time; min:sec [tMS].
5. Choose Remote Timer Start [`rts] to function as;
manual [`off], or remote timer start [tMr].
6. Choose a display default [dISP] (see page 18):
• Actual Temperature only [``Ac]
• Actual; Set Point [AcSP]
• Actual; Time [Acti]
• Time; Actual [tiAc]
• Time; Set Point [tiSP]
7. Choose a Timer Output Function [tIM]:
• Delay ON [dLon]
• Delay off [dLoF]
• Signal ON [sgon]
• Signal off [sgoF]
8. Choose a start timer [Strt] function;
either immediate [IMd], ready band [`rdY],
Ready Acknowledge [rdYA], or Power [PWr].
9. If you chose [`rdY] or [rdya],
then select a ready band [`rdy] value.
10. If you chose [SGon] or [sgof],
then select a signal time [``St] value.
11. Go to the 935B’s Operation Menu.
12. Set the countdown time [tMr].
13. Choose the idle set point [IdLE] to track [trAc]
the primary set point, or select a separate
idle set point value between the range high [``rh]
and range low [``rL] values.
14. Run the system, and test the timer start
with a , press or [`rts] signal.
15. Document the timer settings and system.
Configuration Menu
[``In]
Input Type
[`C_F]
Celsius/Fahrenheit
[``rL]
Input Range Low
[``rh]
Input Range High
[`Ot1]
Output 1 Function
[`Ot2]
✓
Output 2 Function
[`rts]
✓
Remote Timer Start
[dISP]
✓
Display Default
[ALty]
Alarm Type
[AhYS]
Alarm Hysteresis
•
•
•
[tIM]
✓
Timer Function
[Strt]
✓
Start Timer
[`rdY]
✓
Timer Ready Band
[``St]
✓
Signal Time
Operations Menu
[`Aut]
Auto-tune
[tMr]
✓
Countdown Timer
[IdLE]
✓
Idle
Setting the Countdown Timer