Watlow Series 935B User’s Manual 23
Table 8 - Setting Inputs and Outputs
NOTE:
Access to Configuration Menu varies with lockout function. See p. 21.
Input Type - Choose sensor type.
[```J] [```H] [```t] [```n] [```E] [```S] [`rtd] [`r†d]
J t/c K t/c T t/c N t/c E t/c S t/c 1.0° RTD 0.1° RTD
Celsius/Fahrenheit - Choose displayed unit of measure.
[``°F] [``°C]
°F °C
Input Range Low - Select lowest displayable Set Point, dependent on [``In].
[``In] [``rh] Select a value (lowest displayable set point) between
Input Type Range Low and Input Range High.
Input Range High - Select highest displayable Set Point, dependent on [``In].
[``rL] [``In] Select a value (highest displayable set point) between
Input Type Range High and Input Range Low.
Output 1 Function - Choose Output 1 type.
[hEAt] [COOL] [ALM] [nonE]
Heat Cool Alarm None
Output 2 Function - Choose Output 2 type (dependent on Output 1 choice).
[hEAt] [COOL] [ALM] [thM] [tMS] [nonE]
Heat Cool Alarm Timer Timer None
Hr./Min. Min./Sec
Remote Timer Start - Choose Off, Front Panel Lock, or Timer (Hrs:Min).
[`off] [`fpl] [tmr]
Off Front Panel Timer
Lock
Display Default -
Choose the primary (last 2 characters) and secondary (first 2 characters) default displays. Press
ß to toggle to the secondary display for 15 seconds.
[``Ac] [[AcSP]] [Acti] [tiAc] [tiSP]
No secondary Actual temp. Actual temp. Time remaining Time remaining
Actual temp. Set pnt temp. Time remaining Actual temp. Set point temperature
Input Range Information
J t/c: 32 to 1382°F or 0 to 750°C
K t/c: -328 to 2282°F or -200 to 1250°C
T t/c: -328 to 662°F or -200 to 350°C
N t/c: 32 to 2282°F or 0 to 1250°C
S t/c: 32 to 2642°F or 0 to 1450°C
E t/c: -328 to 1470°F or -200 to 799°C
1° RTD (DIN): -328 to 1292°F or -200 to 700°C
0.1° RTD: -99.9 to 999.9°F or -99.9 to 700.0°C
Valid Output Functions
First select Output 1: Then select Output 2:
Heat None, Cool, Alarm, Timer
Cool None, Heat, Alarm, Timer
Alarm None, Heat, Cool
None Heat, Cool, Alarm
• The function of Output 1 determines the options available for
Output 2.
• First select the function of Output 1. Refer to the table (right),
then select the function of Output 2.
[``In]
[`C_F]
[``rL]
[``rh]
[`rts]
[`Ot2]
[dISP]
Configuration Menu
[`Ot1]