Chapter 9: Troubleshooting and Reconfiguring CLS200 Series User’s Guide
186 Watlow Anafaze Doc.# 0600-3050-2000
Table 9.15 Resistor Locations for CLS216
Voltage Inputs
Scaling and Calibration
The controller provides offset calibration for thermocouple,
RTD, and other fixed ranges, and offset and span (gain) cal-
ibration for linear and pulse inputs. In order to scale linear
input signals, you must:
1. Install appropriate scaling resistors. (Contact Watlow
Anafaze’s Customer Service Department for more in-
formation about installing scaling resistors.)
2. Select the display format. The smallest possible range
is -.9999 to +3.0000; the largest possible range is
-9,999 to 30,000.
3. Enter the appropriate scaling values for your process.
Configuring Dual DAC Outputs
Dual DAC modules ship with both outputs configured for
the signal type and span ordered. The module contains two
independent circuits (DAC1 and DAC2). These circuits can
be configured for different output types. Remove the board
from the housing and set the jumpers. The odd numbered
jumpers determine the signal from DAC1; the even num-
bered jumpers determine the output from DAC2.
Resistor Locations Resistor Locations
Loop RC RD Loop RC RD
1 R58 R42 9 R57 R41
2 R56 R40 10 R55 R39
3 R54 R38 11 R53 R37
4 R52 R36 12 R51 R35
5 R50 R34 13 R49 R33
6 R48 R32 14 R47 R31
7 R46 R30 15 R45 R29
8 R44 R28 16 R43 R27