
CLS200 Series User’s Guide Chapter 9:Troubleshooting and Reconfiguring
Doc.# 0600-3050-2000 Watlow Anafaze 181
Figure 9.6 CLS204 and CLS208 Input Circuit
CLS204 and CLS208 Current Inputs
For each current input on a CLS204 or CLS208 controller
you must install a resistor. The value of the resistor must
be correct for the expected input range. Install the resistor
in the listed resistor pack (RP) location. Note the resistor
pack locations have three through holes. Install the resis-
tor as shown in the illustration below.
Table 9.6 Resistor Values for CLS204 and
CLS208 Current Inputs
Resistor tolerance: ±0.1%
Table 9.7 Resistor Locations for CLS204 and
CLS208 Current Inputs
Input Range Resistor Value RD
0 to 10 mA 6.0 Ω
0 to 20 mA 3.0 Ω
Loop
Resistor
Location RD
Loop
Resistor
Location RD
1 RP1 5 RP5
2 RP2 6 RP6
3 RP3 7 RP7
4 RP4 8 RP8
Com
IN-
RC (RTD)
IN+
RD
RP
Analog
Input
Terminal
Internal
RP
+5VÎ (dc)
Reference
To CLS200
Circuitry
RC (Voltage)
+
-
RP#
RD
Comentarios a estos manuales