Chapter 4: Setup CLS200 Series User’s Guide
98 Watlow Anafaze Doc.# 0600-3050-2000
Heat or Cool Linearity
Select an output curve. For a nonlinear process, select
CURVE 1 or CURVE 2.
Selectable values: CURVE 1, CURVE 2, or LINEAR. Refer
to Figure 4.4.
Figure 4.4 Linear and Nonlinear Outputs
If curve 1 or 2 is selected, a PID calculation results in a low-
er actual output level than the linear output requires. One
of the nonlinear curves may be used when the response of
the system to the output device is nonlinear.
ALARM
01 HEAT OUTPUT?
LINEAR
Actual Output
0
20
40
60
80
100
PID Calculation
10
20
30
40
50
60
70
80
90
3
8
13
27
48
62
2
4
7
12
29
44
66
Linear
Curve 1
Curve 2
36
19 19
79
Vista de pagina 113