CLS200 Series User’s Guide Chapter 9:Troubleshooting and Reconfiguring
Doc.# 0600-3050-2000 Watlow Anafaze 185
Table 9.13 Resistor Locations for CLS216
Current Inputs
CLS216 Voltage Inputs
For each voltage input on a CLS216 controller, you must in-
stall two resistors. The resistance must be correct for the
expected input range. Install the resistors in the listed lo-
cations.
Table 9.14 Resistor Values for CLS216
Voltage Inputs
Resistor tolerance: ±0.1%
Loop
Resistor
Location
RD
Loop
Resistor
Location
RD
1 R42 9 R41
2 R40 10 R39
3 R38 11 R37
4 R36 12 R35
5 R34 13 R33
6 R32 14 R31
7 R30 15 R29
8 R28 16 R27
Resistor Values
Input Range RC RD
0 to 100mV
Î
(dc)
499 750
0 to 500mV
Î
(dc)
5.49 k 750
0 to 1V
Î (dc)
6.91 k 442.0
0 to 5VÎ (dc)
39.2 k 475.0
0 to 10VÎ (dc)
49.9 k 301.0
0 to 12VÎ (dc)
84.5 k 422.0