10.4 Diagnostics Watlow Series F4S/D
NOTE: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
Diagnostic Menu Parameter Table (Factory Page) Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default [I/O, Set, Ch] Parameters to Appear
Active: Always.1602 wDefault all values?
Yes (800)
Full Defaults
Causes all parame-
ters and profile val-
ues to revert to
their factory default
settings.
Active: Always.1513 wYes (1)
Display Test
Checks LED display
segments by turning
them on and off.
Active: Always.
NOTE: Must be in the Calibra-
tion or Test Menu at the display
for this prompt to work via com-
munications.
1514 wAll Off (0)
Output 1A (1)
Output 1B (2)
Output 2A (3)
Output 2B (4)
Retransmit 1 (5)
Retransmit 2 (6)
Alarm 1 (7)
Alarm 2 (8)
Digital Out 1 (9)
Digital Out 2 (10)
Digital Out 3 (11)
Digital Out 4 (12)
Digital Out 5 (13)
Digital Out 6 (14)
Digital Out 7 (15)
Digital Out 8 (16)
All On (17)
Communications (18)
Test Outputs
Choose output to
test.
Main > Factory > Test
Test