A.6 WATLOW Series 988LF Users Manual Appendix
Specifications
Line Voltage/Power
100-240Vı(ac/dc) +10%, -15%; 50/60Hz, ±5%
24-28Vı(ac/dc) +10%, -15%; 50/60Hz, ±5%
Power consumption 16VA maximum
Operating Environment
32 to 149°F (0 to 65°C)
0 to 90% RH, non-condensing
Storage Temperature
-40 to 185°F (-40 to 85°C).
Agency Approvals
UL, C-UL File # 43684
CE: 89/336/EEC Electromagnetic Compatibility
Directive.
EN 50081-2: 1994 Emissions.
EN 50082-2: 1995 Immunity.
73/23/EEC Low-Voltage Directive.
EN 61010-1: 1993 Safety.
NEMA 4X
Terminals
#6 compression universal head screws (tighten
to 5 inch/pounds maximum), accepts 20-14
gauge wire.
Accuracy
Calibration accuracy and sensor conformity:
±0.1% of span, ±1 LSD, 77°F ±5°F (25°C ±3°C)
ambient and rated line #voltage ±10%
Accuracy span: 1000°F (540°C) minimum
Temperature stability: ±0.2°F/°F (0.1°C/°C)
change in ambient
Mechanical
1⁄8 DIN panel mount, NEMA 4X (IP65
equivalent) front panel
Overall width x height x depth
Horizontal; 4.03" x 2.18" x 4.74", (102 mm x 55
mm x 120 mm)
Vertical; 2.18" x 4.03" x 4.74", (55 mm x 102
mm x 120 mm)
Depth behind panel; 4.06"(103 mm)
Weight less than or equal to 14.0 oz (0.40kg)
Input Range
Specified temperature ranges represent the
controller's operational span.
Thermocouple
(Available with basic or universal signal
conditioner)
Type C
2
32 to 4200°F or 0 to 2316°C
Type D
2
32 to 4200°F or 0 to 2316°C
Type E -328 to 1470°F or -200 to 799°C
Type J 32 to 1500°F or 0 to 816°C
Type K -328 to 2500°F or -200 to 1371°C
Type N 32 to 2372°F or 0 to 1300°C
Type T -328 to 750°F or -200 to 399°C
Pt 2
2
32 to 2543°F or 0 to 1395°C
(1064)
(Available with universal signal conditioner)
Type B 1598 to 3300°F or 870 to 1816°C
Type R 32 to 3200°F or 0 to 1760°C
Type S 32 to 3200°F or 0 to 1760°C
RTD Resolution (DIN or JIS) (Avail. w/universal signal conditioner)
1° (DIN) -328 to 1472°F or -200 to 800°C
1° (JIS) -328 to 1166°F or -200 to 630°C
0.1° (DIN and JIS)
-99.9 to 999.9°F or -73.3 to 537.7°C
Process (Available with universal signal conditioner)
0-50mVÎ(dc) -999 to 9999 units
0-5VÎ(dc) -999 to 9999 units
1-5VÎ(dc) -999 to 9999 units
0-10VÎ(dc) -999 to 9999 units
0-20mAÎ(dc) -999 to 9999 units
4-20mAÎ(dc) -999 to 9999 units
Output Options
Solid state relay, 0.5A @ 24V~ (ac) min., 253V~
(ac) max., opto isolated, burst fire. With or
without contact suppression.
Open collector, switched dc signal provides a
minimum turn-on voltage of 3VÎ(dc) into a
minimum 500 load; maximum on voltage not
greater than 32VÎ(dc) into an infinite load,
isolated.
Electromechanical relay
1
, Form C, 5A @ 120/
240~ (ac), 6A @ 28VÎ(dc), 1/8 hp. @ 120V~ (ac)
or 125VA @ 120V~ (ac). With or without contact
suppression. Off-state output impedance with
RC suppression is 20k .
Process, 0-20mA (dc), 4-20mA (dc) into 800
maximum, 0-5VÎ(dc), 1-5VÎ(dc), or 0-10VÎ(dc)
into 1k minimum
1
, reverse acting, isolated.
1
Electromechanical relays are warranted for 100,000
closures only. Solid-state switching devices are
recommended for applications requiring fast cycle times or
extended service life.
2
Not an ANSI symbol.