Setup
4.6 WATLOW Series 988LF Users Manual Setup Menu, Chapter 4
[`dEC]
Decimal
Select the decimal point location for process type input 1 data. This
prompt, in conjunction with the Range Low and Range High prompts,
allows you to format and limit units of measure for process 1.
• All prompts with units of measure related to input 1 will display in the
selected decimal format.
• This affects propbands, alarm set points, process set points, calibration
offsets, deadbands and ranges.
[`dEC] This prompt appears only if you have set input 1 [`In1] to a
process input or a thermocouple input set to [0-50] mV.
Default
↓
[```)] [``)0] [`)00} [)000]
[`dEC] [`dEC] [`dEC] [`dEC]
Remote Set Point Input
Enable a remote set point signal. The remote set point input selection
switches are set to process at the factory.
[`rSP] This prompt appears only on controllers equipped with Remote Set
Point Input hardware (98 _ L-_ 2__-AA__).
If Default
↓↓
RSP Input DIP J K T N E W3 W5 Pt2 0-50mV
[`OFF] [``J] [``H] [``t] [``n] [``E] [``C] [``d] [`Pt2] [0-50
[`rSP] [`rSP] [`rSP] [`rSP] [`rSP] [`rSP] [`rSP] [`rSP] [`rSP] [`rSP
thermocouple
RSP Input DIP RSB
[`OFF] [```r] [```S] [``b]
[`rSP] [`rSP] [`rSP] [`rSP]
thermocouple
RSP Input DIP RTD RTD(0.1°)
[`OFF] [`rtd] [`r†d]
[`rSP] [`rSP] [`rSP]
RTD
[`rSP]
O
N
↑
123
[`rSP]
Remote Set Point Input
continued on next page.
O
N
↑
123
O
N
↑
123