Watlow Series 988LF Manual de usuario Pagina 25

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 24
Setup
Setup Menu, Chapter 4 WATLOW Series 988LF Users Manual 4.3
[`In1]
ç
Caution:
Changing the value of
[`In1] changes most
other prompts to the
factory default values.
Verify the correct
sensor type before
making a change.
Failure to follow this
guideline could result in
damage to equipment or
property.
Input 1
Select sensor input type. This selection must match the sensor type
connected to terminals 8, 9 and 10. See Appendix for more information
about sensors.
Changing the value of [`In1] changes all other prompts to the
factory default values, [`LOC] Lock prompt and the [`C_F] prompt
in the Setup Menu. If you change the value, the default warning
[[
[[
[dFLt] will flash in the upper display.
Changes do not take effect automatically after five seconds; you must
press the Mode key µ to enter the selector type change and advance to
the next prompt.
[`In1] This prompt always appears.
If Default
↓↓
98_L-1___-AA__
no DIP J K T N E W5 W3 Pt2 0-50mV
[``J] [``H] [``t] [``n] [``E] [``C] [``d] [`Pt2] [0-50]
thermocouple [``n] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1]
only
98_L-2___-AA__
Input 1 DIP J K T N E W5 W3 Pt2 0-50mV
thermocouple [``J] [``H] [``t] [``n] [``E] [``C] [``d] [`Pt2] [0-50]
[``n] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1] [`In1]
Input 1 DIP R S B
thermocouple [``r] [``S] [``b]
[`In1] [`In1] [`In1]
Input 1 DIP RTD RTD(0.1°)
RTD [`rtd] [`r†d]
[[`In1] [`In1]
Input 1 DIP 4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
process [4-20] [0-20] [`0-5] [`1-5] [0-10]
[`In1] [`In1] [`In1] [`In1] [`In1]
O
N
123
O
N
123
O
N
123
O
N
123
Vista de pagina 24