Watlow Series 922 Retrofit Manual de usuario Pagina 8

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 127
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 7
Series 922
Series 922 Line Voltage Input Control Mode Action Output Set Point Mounting Retrofit
See Notes
Below
922A-ABB0-B000 115/230 VAC
J t/c/Proc Progammable Progammable Dual 0.5A SSR/0.5A SSR Profiling 1/4 DIN F4DH-KKKK-01RG 6, 16
922A-ABB0-C000 115/230 VAC
J t/c/Proc Progammable Progammable Dual 0.5A SSR/0.5A SSR Profiling 1/4 DIN F4DH-KKKK-01RG 6, 16
922A-ACC0-A000 115/230 VAC
J t/c/Proc Progammable Progammable Dual Sw dc/Sw dc Profiling 1/4 DIN F4DH-CCCC-01RG
922A-ACC0-B000 115/230 VAC
J t/c/Proc Progammable Progammable Dual Sw dc/Sw dc Profiling 1/4 DIN F4DH-CCCC-01RG 16
922A-ACC0-C000 115/230 VAC
J t/c/Proc Progammable Progammable Dual Sw dc/Sw dc Profiling 1/4 DIN F4DH-CCCC-01RG 16
922A-AFB0-A000 115/230 VAC
J t/c/Proc Progammable Progammable Dual 4-20MA/0.5A SSR Profiling 1/4 DIN F4DH-FKFK-01RG 6
922A-AFB0-B000 115/230 VAC
J t/c/Proc Progammable Progammable Dual 4-20MA/0.5A SSR Profiling 1/4 DIN F4DH-FKFK-01RG 6, 16
922A-AFB0-C000 115/230 VAC
J t/c/Proc Progammable Progammable Dual 4-20MA/0.5A SSR Profiling 1/4 DIN F4DH-FKFK-01RG 6, 16
922A-BBB0-A000 115/230 VAC
K t/c/Proc Progammable Progammable Dual 0.5A SSR/0.5A SSR Profiling 1/4 DIN F4DH-KKKK-01RG 6
922A-BBB0-B000 115/230 VAC
K t/c/Proc Progammable Progammable Dual 0.5A SSR/0.5A SSR Profiling 1/4 DIN F4DH-KKKK-01RG 6, 16
922A-BBB0-C000 115/230 VAC
K t/c/Proc Progammable Progammable Dual 0.5A SSR/0.5A SSR Profiling 1/4 DIN F4DH-KKKK-01RG 6, 16
922A-BCC0-A000 115/230 VAC
K t/c/Proc Progammable Progammable Dual Sw dc/Sw dc Profiling 1/4 DIN F4DH-CCCC-01RG
922A-BCC0-B000 115/230 VAC
K t/c/Proc Progammable Progammable Dual Sw dc/Sw dc Profiling 1/4 DIN F4DH-CCCC-01RG 16
922A-BCC0-C000 115/230 VAC
K t/c/Proc Progammable Progammable Dual Sw dc/Sw dc Profiling 1/4 DIN F4DH-CCCC-01RG 16
922A-BFB0-A000 115/230 VAC
K t/c/Proc Progammable Progammable Dual 4-20MA/0.5A SSR Profiling 1/4 DIN F4DH-FKFK-01RG 6
922A-BFB0-B000 115/230 VAC
K t/c/Proc Progammable Progammable Dual 4-20MA/0.5A SSR Profiling 1/4 DIN F4DH-FKFK-01RG 6, 16
922A-BFB0-C000 115/230 VAC
K t/c/Proc Progammable Progammable Dual 4-20MA/0.5A SSR Profiling 1/4 DIN F4DH-FKFK-01RG 6, 16
Event Board
A007-1732-18B2 115/230 VAC
Dual 0.5A SSR
Open Bd A007-1732-F4B2
A007-1732-18B8 115/230 VAC
Eight 0.5A SSR
Open Bd A007-1732-F4B8
A007-1732-18C2 115/230 VAC
Dual Sw dc
Open Bd A007-1732-F4C2
A007-1732-18C8 115/230 VAC
Eight Sw dc
Open Bd A007-1732-F4C8
A007-1732-18K2 115/230 VAC
Dual 0.5A SSR
Open Bd A007-1732-F4K2
A007-1732-18K8 115/230 VAC
Eight 0.5A SSR
Open Bd A007-1732-F4K8
Note 1: Retrofit controller requires a substitution of a 100 Ohm DIN RTD sensor.
Note 2: Mounting and dimensions of retrofit controller are different. Verify that sufficient panel space and depth is available.
Note 3: Retrofit controller outputs are different. Add external interposing mechanical or solid state relay if applicable.
Note 4: Retrofit controller has a programmable, not fixed set point. Lock set point using controller's lockout parameter.
Note 5: For DIN rail mounting or sub-panel mounting, purchase DIN rail adapter p/n 0822-0586-P001 for 1/32 DIN or p/n 0822-0586-P002 for 1/16 DIN.
Note 6: Add a quencharc suppressor, Watlow p/n 0804-0147-0000, for inductive loads.
Note 7: Retrofit does not have equivalent action (as example, no manual reset)
Note 8: Retrofit controller does not have dual dial scale.
Note 9: Hardware lockout is not available on retrofit.
Note 10: Retrofit controller does not have user selectable line voltage.
Note 11: Retrofit does not support remote set point or retransmit. If wires are on these pins, select a different retrofit.
Note 12: Retrofit controller does not have user selectable control action.
Note 13: Solid state sensor required for humidity. See http://www.vaisala.com
Note 14: Retrofit controller does not have user selectable control mode.
Note 15: Use auxiliay event board A007-1732-F4B8
Note 16: Retrofit communications are different, consult specifications.
Note 17: Verify retrofit input range matches application.
Watlow Controls 7/19/2004 Page 3
Vista de pagina 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 126 127

Comentarios a estos manuales

Sin comentarios