48
WATLOW Series 922 User's Manual
How To Program the Series 922, Chapter 6
Make photocopies, keep original clean.
Prompt Description Range Default Your Settings
ACCESS = (5) SPCLFUNC
To enter SPCLFUNC parameter, use ACCESS (5) and press ENTER.
C/F/U Enter the unit of measure code. (Celcius/Fahrenheit/Units) C/F/U F
Not displayed if DIP Switch #2 is ON.
TYP Enter actual process display to be shown.
Temperature/Process/Humidity
Dual T/C T T or T T T
Dual RTD T T or T H or T T T
Dual RTD 0.1 T T or T H or T T T
0.1 RTD, Process T P or T V or T T P
T/C, Process T P or T V or T T P
RTD, Process T P or T V or T T P
Dual Process P P or P V or P P P
Not displayed if DIP Switch #2 is ON.
OUT1 Enter the control output for Channel 1, Outputs 1 and 2.
Heat PID/Cool PID HTCL HTCL
Cool PID/Heat PID CLHT
Not displayed if DIP Switch #2 is ON.
OUT2 Enter the control output for Channel 2, Outputs 3 and 4.
Heat PID/Cool PID HTCL HTCL
Cool PID/Heat PID CLHT
Not displayed if DIP Switch #2 is ON. Dependent on TYP.
R1L Enter the Range Low value for Channel 1. Dependent on input selection.
Not displayed is DIP Switch #2 is ON. See your TYP parameter setting.
R1H Enter the Range High value for Channel 1. Dependent on input selection.
Not displayed if DIP Switch #2 is ON. See your TYP parameter setting.
R2L Enter the Range Low value for Channel 2. Dependent on input selection.
Not displayed if DIP Switch #2 is ON. Dependent on TYP. See your TYP parameter setting.
R2H Enter the Range High value for Channel 2. Dependent on input selection.
Not displayed if DIP Switch #2 is ON. Dependent on TYP. See your TYP parameter setting.
AUX1 Enter the Auxiliary Output 1. AUX1 AL Alarm output AL
AUX 1 EV Event output
Not displayed if DIP Switch #2 is ON. Dependent on event board.
AUX2 Enter the Auxiliary Output 2. AUX2 AL Alarm output AL
AUX2 EV Event output
Not displayed if DIP Switch #2 is ON. Dependent on TYP & event board.
ALTYP1 Enter Alarm Type 1. ALTYP1 P Process alarm P
ALTYP1 D Deviation alarm
Not displayed if DIP Switch #2 is ON. Dependent on AUX1 & event board.
ALTYP2 Enter Alarm Type 2. ALTYP2 P Process alarm P
ALTYP2 D Deviation alarm
Not displayed if DIP Switch #2 is ON Dependent on AUX2, TYP & event board.
LAT Enter the Alarm function type. LAT or NLAT NLAT
Not displayed if DIP Switch #2 is ON.
RTD Enter input gain of RTD input channels for different curves. JIS or DIN JIS
Not displayed if DIP Switch #2 is ON. Dependent on input.
ALT Set altitude in feet for humidity mode. 0, 2500, 5000 0
Not displayed if DIP Switch #2 is ON. Dependent on input.
GS Enter the Guaranteed Soak. 0 - 50°C 0
ANLG Enter parameter the Analog retransmit signal represents. C1, C2, SP1, SP2 C1
SCALE Enter millivolts to scale analog retransmit output. 1, 2, 5, 10 1
COM Select between XON/XOFF or ANSI X3.28 protocol. XON or STX STX
Dependent on communications capability.
BAUD Select baud rate for serial communications to run at. 1200, 2400, 1200
Dependent on communications capability. 4800, 9600
COM ID Enter the Communications protocol Identification. 0 - 9 0
Dependent on communications capability and COM = STX.
LOCK Enter the Front panel Lock code. 0 - 2 0
CLR FILE Press ENTER to display FILE?. Enter a file number to clear. 1 - 10 1
RETURN Press the ENTER key to return to the SYSTEM prompt.
Press the MODE key to return to the SPCLFUNC prompt.
SETUP Menu
Table 9 continued
NOTE: Changing these parameter
values will default other parameters
and clear all files. See Page 53 & 54
for details.