Watlow MLS Manual de usuario Pagina 82

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 142
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 81
70 MLS User’s Guide
Setup
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
Thermocouple types (J, K, T, S, R and B).
RTD. Three ranges: RTD1 (Platinum Class A), RTD2 (Platinum
Class B), and RTD3 (Nickel).
Linear and Pulse inputs.
Skip (an input type available for unused channels.) The scanning dis-
play doesn't show loops you've set to Skip.
The next table shows the MLS' input types and ranges.
Input
Type
Fahrenheit
Range
Celsius Range
J -350 to +1400 -212 to +760
K -450 to +2500 -268 to +1371
T -450 to +750 -268 to +399
S 0 to +3200 -18 to +1760
R 0 to +3210 -18 to +1766
B +150 to +3200 +66 to +1760
RTD1 -148.0 to +572.0 -100.0 to +300.0
RTD2 -184 to +1544 -120 to +840
RTD3 -94 to 572 -70 to 300
Pulse 0-2 KHz
Skip Loop is not scanned or displayed.
Linear see the
Linear Scaling section
(this chap-
ter) and
Appendix
.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
06 INPUT TYPE?
J T/C
Vista de pagina 81
1 2 ... 77 78 79 80 81 82 83 84 85 86 87 ... 141 142

Comentarios a estos manuales

Sin comentarios