Watlow SDMA Card Shorted Solid State Relay Detector Manual de usuario

Busca en linea o descarga Manual de usuario para Sensores Watlow SDMA Card Shorted Solid State Relay Detector. Watlow SDMA Card Shorted Solid State Relay Detector User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 2
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
There is concern that if a solid state relay fails, it will
most likely fail in a shorted condition. To minimize this
concern, Watlow Controls has designed a low-cost card
(Watlow P/N 09-2313) that provides a shorted SSR
alarm. It is designed to be used with DC input SSRs,
rated 10 to 40 amps on either a single phase or three-
phase, two-leg system. In addition to the SDMA card, we
strongly recommend semiconductor fuses to protect the
SSR, and a high limit cutout to protect the thermal
system from any runaway conditions.
The SDMA card mounts directly on the solid state relay
and takes its power from the current flowing through the
current transformer. If there is no input command signal
from the temperature control to the SSR, and there is
current flow through the heater, the mechanical relay
alarm output will de-energize. This can be wired through
a customer supplied latching relay and alarm to 120 or
240 volts. Output contact rating of the SDMA mechanical
relay is 0.5 amperes maximum.
Watlow Controls
1241 Bundy Blvd., P.O. Box 5580
Winona, MN 55987-5580
Phone: 507-454-5300, Fax: 507-452-4507
SDMA Card
Shorted Solid State Relay Detector
Data Sheet
0600-0028-0006 Rev A (1632) Made in the U.S.A.
January, 1999
Figure 1 - SDMA Card Dimensions
NOTE: Mount with two 6-32 screws 5/8”
long. (Included with the SDMA card.)
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - SDMA Card

There is concern that if a solid state relay fails, it willmost likely fail in a shorted condition. To minimize thisconcern, Watlow Controls has desig

Pagina 2 - SDMA alarm outputs in series

Load Number of Passes of Load WireCurrent Through Current Transformer2 to 3 Amps 53 to 4 Amps 44 to 5 Amps 35 to 10 Amps 210 to 40 Amps 1S D M AHeater

Comentarios a estos manuales

Sin comentarios