Watlow Series 104 Manual de usuario

Busca en linea o descarga Manual de usuario para Sensores Watlow Series 104. Watlow Series 104 User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 6
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Series 104
Users Manual
On-off Temperature
Controller
1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507, Internet: http://www.watlow.com
Watlow’s Series 104 is an economical open board, on-off
temperature controller with a thermocouple or RTD sensor
input. Installation and setup of the control is simple and
easy.
The Series 104 offers setpot options including integral
or fixed set point. Factory selectable options include electro-
mechanical relay, SSR or switched dc output, dual scale,
and heat or cool control mode.
(1922)
Control Mode
On-off
Nominal switching hysteresis, typically 3°F (1.7°C)
Operator Interface
LED indication of output status
Dial scale calibrated to compensate for sensor non-linearities
Integral set point
Dual temperature scale (°F and °C)
Fixed set point
Manufactured to specified value
Input
Thermocouple or platinum RTD available
Thermocouple with automatic cold junction compensation
Thermocouple may be isolated or grounded
Thermocouple and RTD break protection de-energizes output
2- or 3-wire RTD input, 100, 500 or 1000 @ 0°C calibrated for
0.003850/ °C curve, factory selectable
Output
Solid-state relay, Form A, 0.5A @ 24V~ min., 264V~ maximum,
opto-isolated, zero cross switching
Switched dc signal provides a non-isolated minimum turn-on voltage
of 3VÎ (dc) into a minimum 500 load, maximum on voltage not
greater than 32VÎ (dc)
Electromechanical relay, 8A, Form C, SPDT: 8A @ 240V~ resistive,
8A, 28VÎ (dc) resistive, 240V~ 275 VA pilot duty rated
Accuracy
Adjustable Set Point
Calibration accuracy: ±1% of span, at 77°F ±5°F (25°C ± 3°C)
ambient and rated line voltage ± 1%
Set point accuracy: ±3% of dial scale
Accuracy span: 1000°F (540°C) minimum
Fixed Set Point
Calibration accuracy: ±10°F/±6°C of setting, at 77°F ±5°F (25°C
±3°C) ambient and rated line voltage ±1%
Temperature Stability
Thermocouple: Typically 5µV/°F ambient (9µV/°C ambient) input
referenced
RTD: Typically 0.2°F/°F ambient (0.2°C/°C ambient)
Voltage Stability
±0.01% of span (min span of 1000°F or 540°C) per % of rated line
voltage
Agency Approvals
CE: EN61010 - Safety
EN61326 - Industrial Immunity, Class B Emissions
Installation Category 2, Pollution Degree 2
873 Recognized, File #E43684
Recognized to C22.2 No. 24, File #E43684
Approved for use in commercial cooking applications
Terminals
Sensor input
Screw clamp terminal: 12-26 gauge wire
Power input and control output
#6 screws on barrier strip
Power
120V~, +10%/-15%, 50/60 Hz
230V~ to 240~, +10%/-15%, 50/60 Hz
10VA maximum power
Operating Environment
32 to 131°F (0 to 55°C)
0 to 90% RH, non-condensing
Storage temperature: -4 to 185°F (-20 to 85°C)
Dimensions
Width: 4.5 in (114 mm)
Length: 4.0 in (102 mm)
Depth: 1.5 in (38 mm)
Weight
0.7 lb (0.3kg)
UL
®
is a registered trademark of Underwriters Laboratories, Inc.
Note: Specifications subject to change without notice.
Specifications
General Description
$5.00 Made in the U.S.A.
Printed on Recycled Paper
10% Postconsumer Waste
0600-0004-0008 Rev C
August 2000
Supersedes: 0600-0004-0008 Rev B
TOTAL
3 Year Warranty
Vista de pagina 0
1 2 3 4 5 6

Indice de contenidos

Pagina 1 - Series 104

Series 104User’s ManualOn-off TemperatureController1241 Bundy Boulevard, P.O. Box 5580, Winona, Minnesota USA 55987-5580Phone: +1 (507) 454-5300, Fax:

Pagina 2 - Dimensions

Figure 3a — Series 104 dimensions.Use the following procedure to mount and install theWatlow Series 104 temperature control.1. Locate and drill four 0

Pagina 3 - Input Wiring

3 Watlow Series 104 User’s ManualThermocoupleFigure 2a — Thermocouple wiring.NOTE: When an external device with a non-isolated circuit commonis conn

Pagina 4 - System Example

4 Watlow Series 104 User’s ManualFigure 4 — System wiring examples.12348910111256713Series 104Temperature Controller104C-1601-110045120V~L1L21367891

Pagina 5 - Declaration of Conformity

5 Watlow Series 104 User’s ManualDeclaration of ConformitySeries 104WATLOW WINONA1241 Bundy BoulevardWinona, Minnesota 55987 USADeclares that the f

Pagina 6 - WarrantyOrdering Information

Connect per Input Wiring, page 3.Remove power to the controller and the controller fromthe system. Apply power to the system with the con-troller remo

Comentarios a estos manuales

Sin comentarios