Watlow CPC400 Manual de usuario Pagina 84

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 230
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 83
Chapter 3: Operation and Setup CPC400 Series User’s Guide
70 Watlow Anafaze Doc. 0600-2900-2000
If the primary loop has both heat and cool outputs,
then the set point of the secondary loop is equal to the
Cascade low SP parameter when the cool output is at
100 percent, and is equal to the Cascade high SP when
the heat output is at 100 percent. See Figure 3.9.
If the primary loop has only a heat output, then the set
point of the secondary loop is equal to the Cascade low
SP parameter when the heat output is at 0 percent,
and is equal to the Cascade high SP parameter when
the heat output is at 100 percent. See Figure 3.10.
If the primary loop has only a cool output, then the set
point of the secondary loop is equal to the Cascade low
SP parameter when the cool output is at 100 percent,
and is equal to the Cascade high SP parameter when
the cool output is at 0 percent.
Figure 3.9 Secondary Set Point When Primary
Loop Has Heat and Cool Outputs
Figure 3.10 Secondary Set Point When Primary
Loop Has Heat Output Only
Set Point of Secondary Loop
(Engineering Units)
High Set Point
Low Set Point
-100%
Output of Primary Loop (Percent of Full Scale)
100%
Set Point of the Secondary Loop
(Engineering Units)
High Set Point
Low Set Point
0%
Output of Primary Loop (Percent of Full Scale)
100%
Vista de pagina 83
1 2 ... 79 80 81 82 83 84 85 86 87 88 89 ... 229 230

Comentarios a estos manuales

Sin comentarios