Chapter 5: Menu and Parameter Reference CPC400 Series User’s Guide
98 Watlow Anafaze Doc. 0600-2900-2000
BCD Job Load Logic
Choose which state is considered “true” for the digital in-
puts that are used for remote job selection.
If 1=true is selected, then an input is true if connected
to controller common, and false for an open circuit.
If 0=true is selected, then an input is true for an open
circuit, and false if connected to controller common.
Table 5.4 shows which combinations of input states are re-
quired to load each job.
Values: 1=true (0) or 0=true (1). Values in parentheses are
for serial communications and LogicPro.
Default: 1=true (0)
Modbus Address: 44838
Parameter Number: 113
LogicPro Driver: Database
LogicPro Address: 113.1
Table 5.4 Digital Input States Required to
Load Each Job
Job
Digital Input
1 2 3
1FFF
2TFF
3FTF
4TTF
5FFT
6TFT
7FTT
8TTT
lBCD job load r
logic b1=true