CPC400 Series User’s Guide Chapter 5: Menu and Parameter Reference
Doc. 0600-2900-2000 Watlow Anafaze 107
Table 5.9 Display Formats
Input Range High
For a process or pulse input, enter the high process vari-
able for input scaling purposes. This value will be displayed
when the input signal is at the level set for Input high sig-
nal.
This parameter and the Input high signal parameter to-
gether define a point on the conversion line for the scaling
function. See Setting Up a Process or Pulse Input on page
58.
Values: Any value between Input range low and the maxi-
mum process variable for the selected display format (see
Table 5.9).
Default: 1000. Decimal placement depends upon the value
of the Disp format parameter.
Modbus Address (Loops 1 to 9): 40581 to 40589
Parameter Number: 36
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 36.1 to 36.9
Decimal Placement for Modbus or LogicPro: See Dec-
imal Placement for Numeric Values on page 80.
Input High Signal
For a process or pulse input, enter the input signal level
that corresponds to the value for the Input range high pa-
rameter. For a process input, the high signal is a percent-
age of the full scale input range. For a pulse input, the high
signal is expressed in Hertz.
Values: For process inputs, -99.8 to 999.9 (-998 to 9999)
percent of full scale. For pulse inputs, 1 to 2000 (1 to 2000)
Hz. This value must be greater than the value for Input low
signal. Values in parentheses are for serial communica-
tions and LogicPro.
Default: 100.0% (1000) for a process input, 1000 (1000) for
a pulse input
Display Value
Modbus or
LogicPro
Value
Minimum
Process
Variable
Maximum
Process
Variable
-999 to 3000 255 -999 3000
-9999 to 30000 0 -9999 30000
-999.9 to 3000.0 1 -999.9 3000.0
-99.99 to 300.00 2 -99.99 300.00
-9.999 to 30.000 3 -9.999 30.000
-.9999 to 3.0000 4 -0.9999 3.0000
l01 Input ranger
high b 1000 ˚F
l01 Input high r
signal b100.0%