CPC400 Series User’s Guide Chapter 2: Installation
Doc. 0600-2900-2000 Watlow Anafaze 37
Functions Activated by Digital Inputs
Use digital inputs to activate the following functions:
Load a job that is stored in controller memory. See
BCD Job Load on page 97.
Change all loops to manual mode at specified output
levels. See Mode Override on page 99.
Enable thermocouple short detection. See Thermocou-
ple Short Alarm on page 101.
Restore automatic control after a failed sensor has been
repaired. See Restore Automatic Mode on page 114.
TB18 Connections
Table 2.5 TB18 Connections
1
The indicated outputs are dedicated for control when enabled in the
loop setup. If one or both of the outputs are disabled for a loop, then the
corresponding digital outputs become available for alarms or program-
mable logic.
2
If you install a Watlow Anafaze Serial DAC, the CPC400 series control-
ler uses digital output 34 for a clock line. You cannot use output 34 for
anything else if a Serial DAC is installed.
Control Output
1
Terminal Function CPC404 CPC408
1 +5VÎ (dc)
2 CTRL COM
3 Watchdog timer
4 Global alarm
5 Output 1 Loop 1 heat Loop 1 heat
6 Output 2 Loop 2 heat Loop 2 heat
7 Output 3 Loop 3 heat Loop 3 heat
8 Output 4 Loop 4 heat Loop 4 heat
9 Output 5 Pulse loop heat Loop 5 heat
10 Output 6 Loop 1 cool Loop 6 heat
11 Output 7 Loop 2 cool Loop 7 heat
12 Output 8 Loop 3 cool Loop 8 heat
13 Output 9 Loop 4 cool Pulse loop heat
14 Output 10 Pulse loop cool Loop 1 cool
15
Output 34
2
Serial DAC clock Serial DAC clock
16 Input 1
17 Input 2
18 Input 3/Pulse input