Global Setup Menu
Use the Global setup menu to set parameters that affect all
loops.
Load Setup From Job
Load one of the jobs stored in battery-backed RAM. The fol-
lowing parameters are loaded for each loop as part of a job:
• PID constants, filter settings, set points and hystere-
sis.
• Control mode (automatic or manual) and output power
levels (if the loop is in manual control)
• Alarm functions, set points, hysteresis and delay set-
tings.
• Soft integers 81 to 100 and soft Booleans 237 to 256.
If you have enabled remote job selection (see BCD Job Load
on page 97), you will see the message below, and you will
not be able to use the controller keypad to load a job.
NOTE!
Current settings are overwritten when you select
a job from memory. Save your current settings to
another job number if you want to keep them.
Values: 1 to 8 (1 to 8) or none (0). Values in parentheses are
for serial communications and LogicPro.
Default: none (0)
Modbus Address: 44836
Parameter Number: 111
LogicPro Driver: Database
LogicPro Address: 111.1
Save Setup as Job
Save the current settings as one of eight jobs in the battery-
backed RAM. The following parameters are saved for each
loop as part of a job:
• PID constants, filter settings, set points and hysteresis.
• Control mode (automatic or manual) and output power
levels (if the loop is in manual control)
lGlobal setup r
Other menus b
lLoad setup r
from job bnone
lLoad setup r
not available
lSave setup as r
job bnone