Watlow Series SD31 PID with Optional Countdown Timer Manual de usuario Pagina 22

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 21
Watlow Series SD31 20 Chapter 4 Home
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus.
* Low numbers contain the two lower bytes; high numbers contain the two higher bytes of the four-byte integer.
Decimal precision is set in another parameter.
Caution: Writing to registers continuously, such as ramping set points via comms, will damage the SD31 EEPROM memory. See page 59.
[rP;tg]
Ramp Target Set Point
The target set point for the ramp that is
in process appears in the display after
this prompt appears.
Set Point Low Limit
[SP;Lo]
to Set Point High
Limit
[SP;hi]
NA
Same as
Closed
Loop Set
Point
Controller is ramping.
[Er;In]
Input Error
Indicate an input error state.
None (0)
[----]
Error (1)
NA
24 R
There is an analog in-
put error.
[A1;Lo]
Alarm Low 1 Status
Indicate a low alarm at output 1.
None (0)
Alarm (1)
NA
29 R
There is an Alarm 1
low side alarm.
[A1;hi]
Alarm High 1 Status
Indicate a high alarm at output 1.
None (0)
Alarm (1)
NA
30 R
There is an Alarm 1
high side alarm.
[A2;Lo]
Alarm Low 2 Status
Indicate a low alarm at output 2.
None (0)
Alarm (1)
NA
31 R
There is an Alarm 2
low side alarm.
[A2;hi]
Alarm High 2 Status
Indicate a high alarm at output 2.
None (0)
Alarm (1)
NA
32 R
There is an Alarm 2
high side alarm.
Display Parameter Name
Description
Settings Range
(Integer values for Modbus
in parenthesis.)
Default Modbus*
(less 40,001
offset)
Read/Write
Appears if:
Vista de pagina 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 71 72

Comentarios a estos manuales

Sin comentarios