Watlow Series 96 Wiring ■ 3.3
ç
WARNING:
To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series
96. Failure to do so could
result in injury or death.
ç
CAUTION:
Maintain isolation
between input 1 and
input 2 to prevent a
ground loop. A ground
loop may cause incorrect
readings, dashes across
the upper display or the
display of error codes.
Failure to follow this
guideline could result in
damage to equipment
and product.
ç
**CAUTION:
Process input does not
have sensor break
protection. Outputs can
remain full on.
Input 2 Wiring
Figure 3.3a – **0-5VÎ, 1-5VÎ or 0-10VÎ (dc) Process
Universal signal conditioner
96 _ 1 - _ _ _ _ - _ _ _ _
Input impedance: 20kΩ
Figure 3.3b – **0-20mA or 4-20mA Process
Universal signal conditioner
96 _ 1 - _ _ _ _ - _ _ _ _
Input impedance: 100Ω
Figure 3.3c – Digital Event
96 _ 1 - _ _ _ _ - _ _ _ _
Voltage input
3-36VÎ (dc) Event Input High State
0-2VÎ (dc) Event Input Low State
Contact closure
0-2kΩ Event Input Low State
> 23kΩ Event Input High State