Watlow Series 96 Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
3.6 Wiring Watlow Series 96
Output 3 Wiring
Figure 3.6 – AC Outputs
Electromechanical relay without contact suppression
96 _ _ - _ _ D_ - _ _ _ _
Form C, 2 amps, off-state impedance: 31M
10
8
1
2
3
4
5
6
7
13 14 15
11
12
16 17 18
19 20 21
9
External
Load
L2
L1
11
10
N.C.
N.O.
12
COM.
customer-supplied
Quencharc
NOTE:
Successful installation
requires five steps:
Choose the controller’s
hardware configuration
and model number
(Appendix);
Choose a sensor
(Chapters Three and
Six, and Appendix);
Install the controller
(Chapter Two);
• Wire the controller
(Chapter Three) and
• Configure the controller
(Chapters Four, Five
and Six).
NOTE:
Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, switched dc or
solid-state relay output
options requires use of
an R.C. suppressor.
Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part No.
0804-0147-0000.
ç
WARNING:
To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series
96. Failure to do so could
result in injury or death.
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 71 72

Comentarios a estos manuales

Sin comentarios