Watlow EZ-ZONE
®
RUI/Gateway 24 Chapter 4 RUI Page
Display
Parameter name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Param-
eter ID
Data
Type
& Read/
Write
[iP;g2]
[ip.g2]
Communications 2
IP Fixed Gateway Part 2
Set the router IP address for
the remote network.
0 to 255
0 - - - - - - - - - - - - 17027 uint
RW
[iP;g3]
[ip.g3]
Communications 2
IP Fixed Gateway Part 3
Set the router IP address for
the remote network.
0 to 255
0 - - - - - - - - - - - - 17028 uint
RW
[iP;g4]
[ip.g4]
Communications 2
IP Fixed Gateway Part 4
Set the router IP address for
the remote network.
0 to 255
0 - - - - - - - - - - - - 17029 uint
RW
[iP;g5]
[ip.g4]
Communications 2
IP Fixed Gateway Part 5
Set the router IP address for
the remote network.
0 to 255
0 - - - - - - - - - - - - 17030 uint
RW
[iP;g6]
[ip.g4]
Communications 2
IP Fixed Gateway Part 6
Set the router IP address for
the remote network.
0 to 255
0 - - - - - - - - - - - - 17031 uint
RW
[Mb;E]
[Mb.E]
Communications 2
Modbus TCP Enable
Activate Modbus TCP.
[``no] No
[`YES} Yes
Yes - - - - - - - - - - - - 17041 uint
RWE
[EiP;E]
[EiP.E]
Communications 2
EtherNet/IP™ Enable
Activate Ethernet/IP™.
[``no] No
[`YES} Yes
Yes - - - - - - - - - - - - 17042 uint
RWE
[`Ad;d]
[ Ad.d]
Communications 2
DeviceNet™ Node Address
Set the DeviceNet™ address
for this gateway.
0 to 63
63 - - - - - - - - - - - - 17052 uint
RWE
[bAUd]
[bAUd]
Communications 2
Baud Rate DeviceNet™
Set the speed of this gate-
way's communications to
match the speed of the serial
network.
[`125] 125 kb
[`250] 250 kb
[`500] 500 kb
125 - - - - - - - - - - - - 17053 uint
RWE
[`FC;E]
[ FC.E]
Communications 2
DeviceNet™ Quick Con-
nect Enable
Allows for immediate com-
munication with the scanner
upon power up.
[``no] No
[`YES} Yes
No - - - - - - - - - - - - 17054 uint
RWE
[p;add]
[P.Add]
Communications 2
Profibus Address
Set the Profibus DP address
for this gateway.
[``no] No
[`YES} Yes
No - - - - - - - - - - - - 17060 uint
RWE
[a;loc]
[A.Loc]
Communications 2
Profibus DP address lock
When set to yes will not al-
low address to be changed
using software. Can be
changed from front panel.
[``no] No
[`YES} Yes
No - - - - - - - - - - - - 17061 uint
RWE
[`C_F]
[ C_F]
Communications 2
Display Units
Select which scale to use for
temperature passed over
communications port 2.
[```f] F
[```C} C
F 440 0x96 (150)
2
6
25 17050 uint
RWE