Watlow MICRODIN Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
17 Watlow MicroDIN Quick Start Guide
Wiring Examples
High
temp.
light
146E-1601-1000
Limit Control
Heater
Optional
Normally
Open
Momentary
Switch
DIN-A-MITE
DA10-24C0-0000
High Limit
Mechanical
Contactor
Branch
Circuit Fuse
Semiconductor
Fuse
Earth Ground
L1
120V
Å
(ac)
L2
21
3
4
Watlow
MicroDIN
Temperature
Controller
UD1A-CES-0000
0830-0474-0000
Power Supply
Thermocouples
PC
OR
ModBus
Converter
R
EIA485
Loop
EIA485 to RS232
Converter
Coil
21 3456789
21345678910
1110 121314151617
6
5
(-)
(+)
(-)
(+)
Figure 17 -
System wiring example,
schematic
Ó
WARNING:
To avoid potential elec-
tric shock, use National
Electric Code (NEC) safe-
ty practices when wiring
and connecting this unit
to a power source and to
electrical sensors or
peripheral devices.
Failure to do so could
result in injury or death.
ç
WARNING:
Install high or low tem-
perature limit control pro-
tection in systems where
an over temperature fault
condition could present a
fire hazard or other haz-
ard. Failure to install
temperature limit control
protection where a poten-
tial hazard exists could
result in damage to
equipment and property
and injury to personnel.
Vista de pagina 16