Watlow EZ-ZONE
®
RMH Module 40 Chapter 3 Operations Page
RM High Density Module Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Su;c]
[ Sv.c]
Process Value (1 to 16)
Source Value C
View the value of Source C.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 8254
[offset 70]
0x7E (126)
1 to 16
0x12 (18)
- - - - 26018 float
R
[`Su;d]
[ Sv.d]
Process Value (1 to 16)
Source Value D
View the value of Source D.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 8256
[offset 70]
0x7E (126)
1 to 16
0x13 (19)
- - - - 26019 float
R
[`Su;E]
[ Sv.E]
Process Value (1 to 16)
Source Value E
View the value of Source E.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - - 8258
[offset 70]
0x7E (126)
1 to 16
0x14 (20)
- - - - 26020 float
R
[oFSt]
[oFSt]
Process Value (1 to 16)
Offset
Set an offset to be applied
to this function's output.
-1,999.000 to 9,999.000°F
or units
-1,110.000 to 5,555.000°C
0 8264
[offset 70]
0x7E (126)
1 to 16
0x17 (23)
- - - - 26023 float
RWES
[``o;u]
[ o.v]
Process Value (1 to 16)
Output Value
View the value of this func-
tion block's output.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0 8262
[offset 70]
0x7E (126)
1 to 16
0x16 (22)
- - - - 26022 float
R
[`dio]
[oPEr]
Digital Input/Output Menu
[`do;S]
[ do.S]
Digital Output (1 to 12)
Output State
View the state of this out-
put.
[`off] Off (62)
[``on] On (63)
1832
[offset 30]
0x6A (106)
1 to 12
7
90 6007 uint
R
[`di;S]
[ di.S]
Digital Input (1 to 12)
Input State
View this event input state.
[`off] Off (62)
[``on] On (63)
1840
[offset 30]
0x6A (106)
1 to 12
0xB (11)
- - - - 6011 uint
R
No Dis-
play
Digital Output (1 to 12)
Output State
View the state of this out-
put.
Off (62)
On (63)
- - - - 1832
[offset 30]
0x6A (106)
1 to 12
7
- - - - 6007 uint
R
[`ACt]
[oPEr]
Action Menu
[`Ei;S]
[ Ei.S]
Action (1 to 24)
Event Input Status
View this input state.
[`off] Off (62)
[``on] On (63)
2188
[offset 20]
0x6E (110)
1 to 24
5
140 10005 uint
R
No Dis-
play
Function Key (1)
Function Key State
View current state of func-
tion key 1.
Off (62)
On (63)
- - - - - - - - - - - - - - - - 3024 uint
R
No Dis-
play
Function Key (2)
Function Key State
View current state of func-
tion key 2.
Off (62)
On (63)
- - - - - - - - - - - - - - - - 3030 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E: EEPROM
S: User Set