Watlow PPC-2000 Manual de usuario Pagina 74

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 320
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 73
Chapter 2: Hardware Installation PPC-2000 User’s Guide
50 Watlow Anafaze Doc.# 30002-00 Rev 2.3
A T/C is connected to a single-ended input by wiring the
positive signal lead to the A or B terminal and the negative
signal lead to the analog COM terminal. See Figure 2.32 and
refer to Table 2.13 on page 48.
WARNING!
Thermocouples connected to single-ended inputs
(PPC-2022) must be isolated (ungrounded) and
should not be embedded within heater elements as
some cartridge heaters are constructed.
.
Figure 2.32 Thermocouples Connected to
Single-ended Inputs 1 and 2
Connecting RTDs
Two-wire RTDs are connected between the A and B terminals
of the selected input. They may only be used with a differential
analog input module. A jumper wire must be added on the
terminal board from the B terminal to the COM terminal. See
Figure 2.33 on page 51.
frame ground
1A (input 1+)
Analog COM
2A (input 2+)
shield
(if present)
shield
(if present)
AITB
Vista de pagina 73
1 2 ... 69 70 71 72 73 74 75 76 77 78 79 ... 319 320

Comentarios a estos manuales

Sin comentarios