Watlow 8LS Controller Manual de usuario Pagina 62

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 140
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 61
54 8LS Users Guide
Setup
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
Thermocouple types (J, K, T, S, R, B, and N)
RTD. Two ranges: RTD1 (Platinum class A: DIN 43760-1980,
Alpha=.00385), and RTD2 (Platinum class B: DIN 43760-1980,
Alpha=.00385).
Linear and Pulse inputs.
Skip. Scanning display doesnt show loops you set to Skip.
Selectable range:
See the table below for the input types and ranges
available for the 8LS.
he is editing. Character editing proceeds left to right one character at a time.
Input Type
Fahrenheit
Range
Celsius
Range
J -350 to +1400 -212 to +760
K -450 to +2500 -268 to +1371
T -450 to +750 -268 to +399
S 0 to +3200 -18 to +1760
R 0 to +3210 -18 to +1766
B +150 to +3200 +66 to +1760
N -450 to +2370 -268 to +1299
RTD1 -148.0 to +572.0 -100.0 to +300.0
RTD2 -184 to +1544 -120 to +840
Pulse 0-20 KHz
Skip Loop is not scanned or displayed
Linear See
Linear scaling
section in this chapter
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
1 INPUT
TYPE? J