Parameter Value Range Factory Default
[`Pb1] If [`dFL] is set to [``US]:
0 - 999°F/0 - 555°C/0 - 999 Units 25°F
0 - 99.9°F/0 - 55.5°C/0 - 99.9 Units 2.5°F
0 is set to ON/OFF control. [`HSC] is set to switch diff.
If [`dFL] is set to [``SI]:
0.0 to 999.9% of span 3%
[`rE1] 0.00 to 9.99 repeats/minute 0.00 repeats/minute
0.00 = No Reset. Won't appear if [`Pb1] is set to 0
or [`dFL] is set to [``SI].
[`It1] 0.0 - 99.9 minutes/rpt. 0.00 = No Integral. 00.0 minutes/repeat
Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``US].
[`rA1] 0.00 to 9.99 minutes 0.00 minutes
0.00 = No Rate. Will not appear if [`Pb1] is set to 0
or [`dFL] is set to [``SI].
[`dE1] 0.00 - 9.99 minutes. 0.00 = No Derivative. 0.00 minutes
Won't appear if [`Pb1] is set to 0 or [`dFL] is set to [``US].
[`Ct1] 0.1 to 999.9 5.0 seconds
Won't appear if [`Pb1] = 0, or [`420].
[`Pb2] Same as [`Pb1]. [`Pb2] lower limit = 1, 0.1, 0.01
[`rE2] Same range as [`rE1].
[`It2] Same range as [`It1].
[`rA2] Same range as [`rA1].
[`dE2] Same range as [`dE1].
[`Ct2] Same range as [`Ct1].
[`ALO]
Deviation [``dE] -999 to 0 -999
Process [``Pr] [``rL] to [`AHI] [``rL]
Will not appear if [`Ot2] is set to [``no] or [`Con].
[`AHI]
Deviation [``dE] 0 to 999 999
Process [``Pr] [`ALO] to [``rH] [``rH]
Will not appear if [`Ot2] is set to [``no] or [`Con].
[`CAL] ±180°F/±100°C/±180 Units 0
[`AUt] 0-3 0
Series V4 Software Map
Parameter Value Range Factory Default Appears If:
[`LOC] [```0], [```1], [```2], [```3], [```4]** 0
[``In] [```J], [```H], [```t], [```n], [```J] DIP switch selectable.
[```S], [`rtd], [`r†d], [`0-5], [`420]
[`dEC] 0, 0.0, 0.00 0 [``In] is set to [`0-5]
or [`420]
[`C_F] [```C] or [```F] Dependent on [`dFL] [``In] is set to [```J],
[```H], [```t], [```n],
[```S], [`rtd], or [`r†d]
[``rL] [``rL] to [``rh] Input dependent.
[``rh] [``rh] to [``rL] Input dependent.
[`Ot1] [``ht] or [``CL] [``ht]
[`HSC] 1 - 99, 0.1 - 9.9, 0.01 - 0.99°F 3, 0.3, 0.03°F
1 to 55, 0.1 to 5.5, 0.01 to 0.55°C 2, 0.2, 0.02°C
[`Ot2] [`Con] = Control [`Con]
[`PrA] = Process Alarm
[``Pr] = Process with no alarm message
[`dEA] = Deviation alarm
[``dE] = Deviation with no alarm message
[``no] = None
[`HSA] 1 - 9999, 0.1 - 999.9, 0.01 - 99.99°F 3, 0.3, 0.03°F [`Ot2] is not set to [`Con]
1 - 5555, 0.1 - 555.5, 0.01 - 55.55°C 2, 0.2, 0.02°C or [``no]
[`LAt] [`LAt] or [`nLA] [`nLA] [`Ot2] is not set to [`Con]
or [``no]
[`SIL] [``On] or [`OFF] [`OFF] [`Ot2] is set to [`dEA] or
[``dE]
[`rtd] [`JIS] or [`din] [`din] [``In] is set to [`rtd] or
[`r†d]
[`rP`] [`Str] is set to Ramping on power up [`OFF]
[``on] is set to Ramping to set point always
[`OFF] is set to None
[`rt`] 0 to 9999 100°/hr [``rP] is not set to [`OFF]
[`P`L] 0 to 100 100
[`dsP] [`nor] = normal [`nor]
[`SEt] = Set Point (lower only)
[`Pro] = Process (upper only)
Setup Menu
Operation Menu
**LOC Functions
[```0]
: All operating parameters may be viewed or changed. Manual operation is permitted. Bumpless transfer to manual
mode will occur on sensor break.
[```1]
: The set point, actual, and alarm settings are only visible parameters, set point is adjustable in this level. Manual
operation and auto-tune are permitted. Bumpless transfer to manual mode will occur on sensor break.
[```2]
: The set point, actual, and alarm settings are the only visible parameters, set point is adjustable in this level. Manual
operation is permitted. Bumpless transfer to manual mode will occur on sensor break.
[```3]
: The set point and actual are the only visible parameters, set point is adjustable in this level. Manual operation is not
permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.
[```4]
: The set point and actual are the only visible parameters, set point is not adjustable in this level. Manual operation is
not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.