Watlow Series SD6 Limit with DeviceNet 16
Table 25. Operational Object Class Attributes
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
1 Get Revision UINT Revision of this object The revision level of this
object (currently 1)
2 Get Max Instance UINT Max allowed Instances Always 1 for this Class
Class Services:
0x0E GET ATTRIBUTE SINGLE
Instance Services:
0x0E GET ATTRIBUTE SINGLE
0x10 SET ATTRIBUTE SINGLE
Operational Object
Class Code: 66hex
Operational Object
The Operational Object access parameters used during nor-
mal day-to-day operation. These are parameters that nor-
mally appear as part of the Operations Page when using the
controller’s front panel.
Table 24. Revision History
Revision Description
01 Initial Release
Attribute # Access
Rule
Name DeviceNet
Data Type
Description of Attribute Semantics of Values
168 Get/Set Process Volts Low Error DINT Sets the low threshold for
input errors when using volt-
age inputs
0.50 to 5.00 V
(default 0.50)
171 Get/Set Process Volts High Error DINT Sets the high threshold for
input errors when using volt-
age inputs
5.00 to 10.00 V
(default 10.00)
169 Get/Set Process Millivolt Low
Error
DINT Sets the low threshold for
input errors when using milli-
volt inputs
5.00 to 25.00 mV
(default 5.00)
172 Get/Set Process Millivolt High
Error
DINT Sets the high threshold for
input errors when using milli-
volt inputs
25.00 to 50.00 mV
(default 50.00)