How to Check for Ground Loops
To check for ground loops, disconnect the ground wire at the ground termina-
tion. Measure the resistance from the wire to the point where it was
connected-
The ohmmeter should read a high ohm value.
If
you have a low ohm value
across this gap, that means there is at least one ground loop present in your
system.
Also, check for continuity; your reading should be “open”.
If you do find conti-
nuity, you must now begin looking for the ground loops. Begin disconnecting
grounds in the system one at a time, checking for continuity after each discon-
nection. When continuity reads “open” you have eliminated the ground loop(s).
Also as you reconnect grounds, keep making the continuity test. It is possible
to reconnect a ground loop.
Noise Suppression Devices
Available from Watlow
Watlow Controls stocks a few key noise suppression parts. You may order
these by calling your local Watlow distributor.
Table 7
-
Noise
Suppression
Device
Ratings.
Item
Electrical
Ratings
Common Mode Line Filter
250V,
3 Amp
Metal
Oxide
Varistor
15OV,
80
Joule
Part Number
0804-0196-0000
0802-0273-0000
I
MOV
I
130V,
38 Joule
1
0802-0304-0000
1
MOV
275V,
75 Joule
0802-0266-0000
MOV
275V,
140 Joule
0802-0405-0000
Line Filtering Configurations For Controls
J
NOTE:
For
very
“dirty” or
critical
applications,
use micro-com-
puter-regulated
power
supply
of
Uninterruptable
Power Supply
(U.P.S.)
These three diagrams show you filter configurations for removing input power
noise. Choose the one best suited for your system if you are unsure which one
to use.
j
22
WATLOW
Series Manual
920 User's
Maual