Watlow Series 92 Manual de usuario Pagina 6

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 13
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 5
6 WATLOW Series 92 User's Manual
Input Wiring
NOTE:
When an external device with a non-
isolated circuit common is connected
to the DC (open collector) output, you
must use an isolated or ungrounded
thermocouple.
k NOTE:
Jumper Terminals 11 and 12
for a 2 wire RTD.
2 Wire RTD 3 Wire RTD
NOTE:
Long lead lengths create electrical resistance. There will be approximately +2°C input error for every 1 of lead
length resistance, when using a two wire RTD. That resistance, when added to the resistance of the RTD element,
can result in erroneous input to the instrument. To overcome this problem, use a three wire RTD sensor, which
compensates for lead length resistance. When extension wire is used for a three wire RTD, all three extension wires
must have the same electrical resistance. (i.e. same gauge, copper stranded.)
Figure 7 - RTD Wiring
Figure 6 - Thermocouple Wiring
k
10 11 12 13 14 15 16 17
+
-
Red
92XX - XXP1 - X0XX 92XX - XXP1 - X0XX
92XX - XXJ1 - X0XX
92XX - XXJ2 - X0XX
92XX - XXK1 - X0XX
92XX - XXT1 - X0XX
10 11 12 13 14 15 16 17
S1
S2
10 11 12 13 14 15 16 17
S1
S2
S3
Vista de pagina 5
1 2 3 4 5 6 7 8 9 10 11 12 13

Comentarios a estos manuales