Watlow EZ-ZONE PM Integrated Controller Manual de usuario Pagina 34

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 181
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 33
Watlow EZ-ZONE
®
PM Integrated Controller 31 Chapter 2 Install and Wire
Warning: Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or
peripheral devices. Failure to do so
may result in damage to equipment
and property, and/or injury or loss
of life.
Note:
Maximum wire size termination and
torque rating:
0.0507 to 3.30 mm
2
(30 to 12
AWG) single-wire termination or
two 1.31 mm
2
(16 AWG)
0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent
ground loops.
Note:
The control output common termi-
nal and the digital common terminal
are referenced to different voltages
and must remain isolated.
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only. Temperature Code T4A
Warning:
ç
Explosion Hazard - Dry contact clo-
sure Digital Inputs shall not be used
in Class I Division 2 Hazardous Loca-
tions unless switch used is approved
for this application.
Warning:
ç
Explosion Hazard – Substitution of
component may impair suitability
for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not discon-
nect while the circuit is live or
unless the area is known to be free
of ignitable concentrations of flam-
mable substances.
Output 1, 3 Switched DC/Open Collector
dc - (open collector)
dc +
common
X_
W_
Y_
Slot A, B
Switched DC
• 30mAdcmaximumsupplycur-
rent
• Shortcircuitlimitedto<50mA
• 22to32VÎ (dc) open circuit volt-
age
• Usedc-anddc+todriveexter-
nal solid-state relay.
• DIN-A-MITEcompatible
• Single-pole:upto4inparallelor
4 in series
• 2-pole:upto2inparallelor2in
series
• 3-pole:upto2inseries
Open Collector
• 100mAmaximumoutputcur-
rent sink
• 30VÎ (dc) maximum supply volt-
age
• Anyswitcheddcoutputcanuse
the common terminal.
• Useanexternalpowersupplyto
control a dc load, with the load
positive to the positive of the
power supply, the load negative
to the open collector and com-
mon to the power supply nega-
tive.
Output 1: (X1,-W1,+Y1)
PM _ _ _ [C] _ - _ _ _ _ _ _ _
Output 3: (X3,-W3,+Y3)
PM _ _ _ _ _ - _ _ [C] _ _ _ _
Switched DC
dc +
dc -
common
24V
X
_
W
_
Y
_
Open Collector
Load
Power Supply
dc -
common
24V
X
_
W
_
Y
_
Output 1, 3 Mechanical Relay, Form C
normally open
normally closed
common
L_
K_
J_
Slot A, B
• 5Aat240VÅ (ac) or 30VÎ (dc)
maximum resistive load
• 20mAat24Vminimumload
• 125VApilotdutyat120/240VÅ
(ac), 25 VA at 24VÅ (ac)
• 100,000cyclesatratedload
• Outputdoesnotsupplypower.
• forusewithacordc
See Quencharc note.
Output 1: (L1,K1,J1)
PM _ _ _ [E] _ - _ _ _ _ _ _ _
Output 3: (L3,K3,J3)
PM _ _ _ _ _ - _ _ [E] _ _ _ _
normally open
common
normally closed
L
_
K
_
J
_
Output 1, 3 Universal Process
volts or current -
current +
volts +
F_
G_
H_
Slot A, B
• 0to20mAinto800Ωmaxi-
mum load
• 0to10VÎ(dc)into1kΩmini-
mum load
• scalable
• outputsuppliespower
• cannotusevoltageandcurrent
outputs at same time
• Outputmaybeusedasre-
transmit or control.
Output 1: (F1,G1,H1)
PM _ _ _ [F] _ - _ _ _ _ _ _ _
Output 3: (F3,G3,H3)
PM _ _ _ _ _ - _ _ [F] _ _ _ _
negative
volts +
current +
4 to 20 mA
0 to 10 V
F
_
G
_
H
_
Quencharc Note:
Switching pilot duty inductive loads
(relay coils, solenoids, etc.) with the
mechanical relay, solid state relay or
open collector output options requires
use of an R.C. suppressor.
Vista de pagina 33