DIN-A-MITE C Ordering Information
To order, complete the code number on the right with the information below:
Style C solid-state power controller
Phase
1=single-phase, 1 controlled leg
2=3-phase, 2 controlled legs
3=3-phase, 3 controlled legs (use with four-wire wye)
8=2 independent zones (input control C, K)
9=3 independent zones (input control C, K)
Cooling and Current Rating Per Leg
0=Natural convection standard DIN rail or panel heatsink
1=Fan-cooled 120VÅ (ac) standard DIN rail or panel heatsink
2=Fan-cooled 240VÅ (ac) standard DIN rail or panel heatsink
3=Fan-cooled 24V
Î (dc) fan standard DIN rail or panel heatsink
T=Natural convection through-wall or cabinet heatsink (UL 50)
Line and Load Voltage
02 = 24 to 48VÅ (ac) (Input Control Signal C, F, or K only)
12 = 100 to 120VÅ (ac) (Input Control Signal L, P or S only)
20 = 200 to 208VÅ (ac) (Input Control Signal L, P or S only)
24 = 120 to 240VÅ (ac) (Input Control Signal C, F or K only);
230 to 240VÅ (ac) (Input Control Signal L, P or S only)
27 = 277VÅ (ac) (Input Control Signal L, P or S only)
40 = 400VÅ (ac) (Input Control Signal L, P or S only)
48 = 480VÅ (ac) (Input Control Signal L, P or S only)
60 = 277 to 600VÅ (ac) (Input Control Signal C, F or K only);
600VÅ (ac) (Input Control Signal L, P or S only)
Input Control Signal
C0 = 4.5 to 32VÎ (dc) contactor
K1 = 22 to 26VÅ contactor
K2 = 100 to 120VÅ contactor
K3 = 200 to 240VÅ contactor
F0 = Proportional 4 to 20 mA (loop powered)
L(0 to 5) = Phase angle with current limiting (DC1 only, Alarm 0 only,
includes one current transformer - Single phase only)
P(0 to 5) = Phase angle (DC1 only, Alarm 0 only - Single phase only)
S(0 to 5) = Single-cycle variable time base
(Select one of the following input options for L, P, S, (0 to 5))
0 = 4 to 20mA
1 = 12 to 20mA (for Input Control Signal option S only)
2 = 0 to 20mA
3 = 0 to 5VÎ (dc) proportional
4 = 1 to 5VÎ (dc) proportional
5 = 0 to 10VÎ (dc) proportional
Alarm
0=No alarm
S=Shorted-SCR alarm (not available on Phase options 8 & 9 or Control options L & P)
H=Open-heater and shorted-SCR alarm (for Input Control Signal option S only)
User Manual Language
0=English
1=German
2=Spanish
3=French
Custom Part Numbers
00 = Standard part
1X = 1-second soft start (control option P, L)
XX = Any letter or number, custom options, labeling, etc.
4
WATLOW DIN-A-MITE Style C User's Manual
__ __ __ __ - __ __ __ __ - __ __ __ __
D C
Current Rating Table
Model Current
(first 4 digits at 50°C
of part number) (122°F)
D
C10 55 A
DC1T 62 A
DC11, DC12, DC13 75 A
D
C20, DC80 40 A
DC2T, DC8T 46 A
D
C21, DC22, DC23 65 A
DC81, DC82, DC83
DC30, DC90 30 A
D
C3T, DC9T 35 A
DC31, DC32, DC33 55 A
D
C91, DC92, DC93
Note:
• Recommended fusing
options to meet 200KA
SCCR, type 1 and 2
approved. All other
fuse and SCR com-
binations are de-
faulted to 5KA SCCR
per UL508A and NEC
guidelines.
Not CE compliant
for conducted or
radiated emissions
Semiconductor Fuses for Applications Through 600VÅ (ac):
Semiconductor Watlow Fuse Bussman Fuse Watlow Holder Ferraz Holder
Fuse Rating P/N P/N P/N P/N
30A 17-8030 FWP30A14F 17-5114 USM141i
40A 17-8040 FWP40A14F 17-5114 USM141i
50A 17-8050 FWP50A14F 17-5114 USM141i
63A 17-8063 FWP63A22F 17-5122 US221i
80A 17-8080 FWP80A22F 17-5122 US221i
100A 17-8100 FWP100A22F 17-5122 US221i
Comentarios a estos manuales