WATLOW DIN-A-MITE Style C User's Manual
17
VÅ
13
14
Triac
RY1
Coil
Reset Switch
RY1A
L1
L2
RY1B
Normally open
Common
Normally closed
(External alarm relay
contacts, set A)
(External alarm relay
contacts, set B)
Latching Alarm Relay Circuit
System Wiring Example Ungrounded Delta or Wye Load 3-phase, 2-leg DIN-A-MITE
NOTE: The current transformers must be in the controlled legs on a 2-leg DIN-A-MITE. The
load wires must pass through the current transformers in the same direction.
Non-latching Alarm Option
(models DC_ _ -
_ _ S _ - H _ _ _ )
Open Heater and Shorted SCR Alarm
The shorted SCR detector compares the input
command signal and actual load current. If
load current is present without an input signal
then the shorted SCR alarm will energize a
triac (on board the DIN-A-MITE) output.
An open-heater or partial open-heater state is
detected when a command signal is present
and a reduced or no output current is detected.
The alarm output is then energized.
This is a non-latching alarm. This output can
be used to drive various indication devices,
such as a coil, light, buzzer, etc. See the
alternative latching circuit section below.
S
emiconductor
Fuses
High-limit
C
ontactor (CR1)
Current
Transformers
Delta
Load
Ungrounded
Wye Load
6
54
V~
(ac)
120 or 240V~ (ac)
@ 300mA maximum
e
nergizes on alarm
From Temperature Control
Pin Y1+, W1- (page 16)
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1 2 3
4 5 6
S
ignal Alarm
G
ain
Bias
Open
H
eater
L
imit
+
-
+
-
+
-
ALM
A
LM
C
T1
CT1
C
T2
CT2
C
T3
CT3
A
djustment
P
otentiometers
Alarm Relay
or Indicator
1A
DIN-A-MITE
D
C20-48S0-H000
2-Leg
Zone
1
Z
one
2
Z
one
3
black
white