70 Communications Specification
Chapter 3: Controller Parameter Descriptions
Output Linearity Curve (69)
This parameter lets users set heat and cool outputs to one of two
nonlinear output curves, or to Linear (no curve).
Range: Users can select 0 for no curve (linear), 1 for a slight curve,
and 2 for a more pronounced curve.
Default: 0 (no curve).
SDAC Mode (70)
This parameter toggles the SDAC between current and voltage output.
Range: 0 to 1, where 0 = voltage and 1 = current.
Default: 0.
SDAC Low Value (71)
This parameter sets a low range value for the output device. This value
must be less than the SDAC high value.
Range: 0 to 999 for voltage outputs and 0 to 1999 for milliamp out-
puts.
Default: 000 (0.00 volts) or 400 (4.00 mA).
SDAC High Value (72)
This parameter sets a high range value for the output device. This value
must be greater than the SDAC low value.
Range: 1 to 1000 for voltage outputs and 1 to 2000 for current out-
puts. (The controller displays this value with a fixed decimal place,
so the user sees a range of 1 to 10.00 for voltage inputs and 1 to
20.00 for current outputs.)
0
100
Linear
Curve 1 Curve 2