Watlow CLS Manual de usuario Pagina 79

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 78
Setup
CLS Users Guide 71
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
Thermocouple types (J, K, T, S, R, B and E).
RTD (4 and 8CLS). Two ranges: RTD1 (Platinum Class A) and
RTD2 (Platinum Class B).
Linear inputs.
Skip (an input type available for unused channels.) The scanning dis-
play doesn't show loops you've set to Skip.
The following tables show the input types and ranges.
Input Type
Range in
º
F Range in
º
C
* Accuracy:
25
º
C
Ambient
* Accuracy:
0-50
º
C Full
Temp. Range
º
C
º
C
º
F
º
C
º
F
J T/C -350 to 1400 -212 to 760
±
0.5
±
0.9
±
1.1
±
2.0
K T/C -450 to 2500 -268 to 1371
±
0.6
±
1.2
±
1.35
±
2.7
T T/C -450 to 750 -268 to 399
±
1.3
±
2.4
±
2.9
±
5.4
S T/C 0 to 3200 -18 to 1760
±
2.5
±
4.5
±
5.6
±
10.1
R T/C 0 to 3210 -18 to 1766
±
2.5
±
4.5
±
5.6
±
10.1
B T/C 150 to 3200 66 to 1760
±
6.6
±
12.0
±
14.9
±
27.0
E T/C -328 to 1448 -200 to 787
Pulse 0-2 KHz
Skip Loop is not scanned or displayed
Linear See the Linear Scaling section
* True for 10% to 100% of span.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
01 INPUT
TYPE ? J T/C