Watlow CLS Manual de usuario Pagina 75

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 74
Setup
CLS Users Guide 67
Keyboard Lock Status
Use this menu to lock the front panel operator function keys
Change
SP, Man/Auto
, and
Ramp/Soak
so that pressing these keys has no
effect. If you want to use these functions, turn off the Keyboard Lock.
Selectable values:
On or Off.
Power-Up Output Status
Use this menu to set the initial power-up state of the control outputs to
Off or Memory. If you choose Off, all control outputs are initially set to
Manual mode at 0% output level. If you choose Memory, the outputs are
restored to the last output state stored in memory.
WARNING
Do not set the CLS to start from memory if a memory-
based restart is unsafe for your process.
Selectable values:
Off or Memory.
Controller Address
Use this menu to set the CLS address. The controller address is used for
multiple controller communications on a single 485 cable, so each CLS
must have a different address. Begin with address 1 for the first
controller and assign each subsequent controller the next higher address.
Selectable values:
1-32.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
KEYBOARD LOCK
STATUS ? OFF
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
POWER UP OUTPUT
STATUS ? OFF
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
CONTROLLER
ADDRESS ? 1
Vista de pagina 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80 ... 179 180

Comentarios a estos manuales

Sin comentarios