Introduction
CAS User’s Guide 3
Specifications
This section contains specifications for inputs, serial interface, system
power requirements, environmental specifications, and physical
dimensions.
Analog Inputs
Number of Analog Inputs: 16 single-ended/ common ground, plus one
pulse input.
Input Switching: solid state MUX switching.
Input Sampling Rate: 1.5x/second (667 ms) at 60 Hz; 1.25x/second
(300 ms) at 50 Hz.
Analog Over Voltage Protection: ±20 V referenced to digital ground.
A/D Converter: Integrates voltage to frequency.
Input Range: -10 to +60 mV. Other ranges are available with scaling
resistors.
Resolution: 0.006%, greater than 14 bits. (This is the internal
measurement resolution, not the display resolution.)
Calibration: Automatic zero and full scale.
T/C Break Detection: Pulse type for upscale break detection.
Milliamp inputs: 0-20 mA (3 ohms resistance) or 0-10 mA (6 ohms
resistance), with scaling resistors.
Thermocouple Ranges and Accuracy
T/C Type Range in ºFRange in ºC *Accuracy:
25ºC
Ambient
*Accuracy:
0 - 50º C Full
Temp. Range
ºC ºF ºC ºF
J T/C -350 to 1400 -212 to 750 ±0.5 ±0.9 ±1.1 ±2.0
K T/C -450 to 2500 -268 to 1371 ±0.6 ±1.2 ±1.35 ±2.7
T T/C -450 to 750 -268 to 399 ±1.3 ±2.4 ±2.9 ±5.4
S T/C 0 to 3200 -18 to 1760 ±2.5 ±4.5 ±5.6 ±10.1
R T/C 0 to 3210 -18 to 1766 ±2.5 ±4.5 ±5.6 ±10.1
B T/C 150 to 3200 +66 to 1760 ±6.6 ±12.0 ±14.9 ±27.0
N T/C -450 to 2370 -268 to 1299 ±1.0 ±1.8 ±2.25 ±4.1
PL-II T/C +50 to 2012 +10 to 1100 ±0.6 ±1.0 ±1.2 ±2.2
* True for 10% to 100% of span.