Watlow 8PID Controller Manual de usuario Pagina 53

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 55
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 52
12
3.8 WRITING ALL OUTPUT LINES
All 16 possible output Lines may be set or cleared simultaneously with one command.
The desired level of each line [1=High(ON) 0=Low(OFF)] is represented by one bit in a
hexadecimal byte representing each four-line group. Refer to Section 3.10 for further
explanation of this compressed data format.
To set the level of all output lines with one command:
XOF (abcd) <CR>
O is the Output indicator
F is the Fast write indicator
a is the value for output lines 15-12
b is the value for output lines 11-08
c is the value for output lines 07-04
d is the value for output lines 03-00
Example:
Command :
XOF0000 <CR>
Set all outputs low (off).
Response:
XOF0000 <CR><LF>
Command :
XOF1111 <CR>
Set lines 12, 08, 04, and 00 high (on).
Response:
XOF1111 <CR> <LF>
Example Command Construction:
Turn ON Lines 15, 14, 13, 12, 09, 04, 02
Turn OFF Remaining Lines
I/O Line Nr | 15 14 13 12 | 11 10 09 08 | 07 06 05 04 | 03 02 01 00
Binary Value| 1 1 1 1 | 0 0 1 0 | 0 0 0 1 | 0 1 0 0
Hex Value | F | 2 | 1 | 4
Dec Value | 15 | 2 | 1 | 4
ASCII Char | ? | 2 | 1 | 4
Resulting Command:
XOF?214 <CR>
Vista de pagina 52
1 2 ... 48 49 50 51 52 53 54 55

Comentarios a estos manuales

Sin comentarios