Watlow 8PID Controller Manual de usuario Pagina 36

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 55
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 35
31
Example:
Command: T1R00090CR sets cycle time to about 5 seconds
Response: TR00090CRLF cycle time is about 5 seconds
To query the cycle time:
T1RQCR
7.5 DIGITAL INPUT AND OUTPUTS
To set the digital outputs and query the digital outputs and digital input:
M(a)(b) M is the digital input output command
a is the I/O number as follows:
1 is output 1
2 is output 2
3 is input only, b must = Q
b is the command as follows:
O is output on (1&2 only)
F is output off (1&2 only)
Q is status query
Example:
Command: M1OCR turn on output 1
Response: M1OCRLF output 1 is on
Example:
Command: M1QCR check status of output 1
Response: M1OCRLF output 1 is on
Example:
Command: M3OCR
incorrect command
digital input cannot be set
Response: .CRLF response to incorrect command
7.6 ANALOG INPUTS
To read the analog input one input at a time
S(n)CR S is the scan command
n is the loop number
The response is in degrees F for thermocouple inputs with resolution to 0.1 F. For all
other inputs on the millivolt scale the response is in percent of full scale with resolution
of 0.01%. A plus or minus sign follows the loop number.
Vista de pagina 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 54 55

Comentarios a estos manuales

Sin comentarios