Watlow Series V4T Manual de usuario Pagina 23

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 26
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 22
Watlow Series V4 23
Specifications (1968)
Control Mode
Microprocessor-based, user selectable control
modes
Single process input, dual output
2.5Hz input sampling rate
1Hz display update rate
Ramp to set point: 0 to 9999 degrees or units per
hour
Heat and cool auto-tune operator interface
Operator Interface
Sealed membrane front panel
Dual, four-digit red or green displays
Advance, ¿Up-arrow, ¯Down-arrow, and
ˆInfinity keys
User selectable screen display
Accuracy
Calibration accuracy and sensor conformity: ±0.1%
of span, ±1°C @ 77°F ± 5°F (25°C ± 3°C) ambient
and rated line voltage
Accuracy span: 1000°F (540°C) minimum
Temperature stability: ±0.2°F/°F (±0.2°C/°C) rise in
ambient maximum
Sensors/Inputs
Thermocouple, grounded or ungrounded sensors
RTD 2- or 3-wire, platinum, 100 @ 0°C calibration
to DIN curve (0.00385//°C) or JIS curve
(0.003916//°C); user selectable
Process, 4-20mA @ 5, or 0-5VÎ (dc) @ 10k
input impedance
Sensor break protection de-energizes control output
to protect system or selectable bumpless transfer to
manual operation
°F or °C or process units display, user selectable
Input Range
Specified temperature ranges represent the
controller’s operational span.
Thermocouple
Type J 32 to 1382°F or 0 to 750°C
Type K -328 to 2282°F or -200 to 1250°C
Type N 32 to 2282°F or 0 to 1250°C
Type S 32 to 2642°F or 0 to 1450°C
Type T -328 to 662°F or -200 to 350°C
RTD Resolution (DIN or JIS)
-328 to 1292°F or -200 to 700°C
0.1° -199.9 to 999.9°F or -128.8 to 537.7°C
Process
4-20mA @ 5 or -999 to 9999 units
0-5V (dc) @ 10k or -999 to 9999 units
Output 1 (Heating or Cooling)
Electromechanical relay
1
. Form C, rated at 8A @
125V~ (ac) or 5A @ 240V~ (ac) or 5A @ 30VÎ (dc),
max. at resistive load, without contact suppression.
Max. switching current is 10A, max. switching power
is 2500VA, and max. switching voltage is 277V~
(ac) or 110VÎ (dc).
Switched dc signal provides a non-isolated minimum
turn on voltage of 3VÎ (dc) into a minimum 500
load; maximum on voltage not greater than 12VÎ
(dc) into an infinite load.
4-20mA reverse or direct acting, non-isolated 0 to
800 load.
Solid-state relay
3
, Form A, 0.5A @ 24V~ (ac) min.,
264V~ (ac) max., opto-isolated burst fire switched,
without contact suppression. Off-state output
impedance is 31M.
Output 2 (Heat, Cool or Alarm)
Electromechanical relay
1
. Form C, rated at 8A @
125V~ (ac) or 5A @ 240V~ (ac) or 5A @ 30VÎ (dc),
max. at resistive load, without contact suppression.
Max. switching current is 10A, max. switching power
is 2500VA, and max. switching voltage is 277V~
(ac) or 110VÎ (dc).
Switched dc signal provides a non-isolated minimum
turn on voltage of 3VÎ (dc) into a minimum 500
load; maximum on voltage not greater than 12VÎ
(dc) into an infinite load.
Solid-state relay
3
, Form A, 0.5A @ 24V~ (ac) min.,
264V~ (ac) max., opto-isolated burst fire switched,
without contact suppression. Off-state output
impedance is 31M.
Alarm output can be latching or non-latching, and
process or deviation with separate high and low
values. Alarm silencing (inhibit) on power up (for
deviation alarms only).
Output Configurations
Output 1
User selectable as: on/off: P, PI, PD, PID, heat or cool
action
Adjustable switching differential: 1 to 99°F (1 to
55°C)
Proportional band: 0 (off) or 1 to 999°F (0 to 555°C)
or 0.0 to 999.9 units
Integral: 0 (off) or 0.1 to 99.9 minutes per repeat
Reset: 0 (off) or 0.01 to 9.99 repeats per minute
Rate/derivative: 0 (off) or 0.01 to 9.99 minutes
Cycle time: 0.1 to 999.9 seconds
Output 2
User selectable as: Control with action opposite that of
Output 1 (heating or cooling)
Process or deviation alarm with flashing alarm
message
Process or deviation alarm without alarm message
Alarm with separate high and low set points
Hysteresis: 1 to 9999° or units switching differential
Line Voltage/Power
100-240V~ (ac), -15%, +10%; (85-264V~ [ac])
50/60Hz, ±5%
14-24Vı (ac/dc), +10%, -15%; (12-26Vı [ac/dc])
50/60Hz, ±5%
Fused internally (factory replaceable only) Slo-Blo®
type (time-lag):
1A, 250V for high voltage versions
2A, 250V for low voltage versions
Maximum power consumption: 12VA (100 to 240V~
[ac]), 7VA (12 to 24Vı [ac/dc])
Data retention upon power failure via non-volatile
memory