EZ-ZONE PM Express (PID) 32 Specifications
Specifications (cont.)
Output Hardware
Switched dc, 22 to 32VÎ(dc) with a maximum of 30 mA supply current available.
Open collector, maximum sink current 100 mA, @ 30VÎ(dc)
Solid state relay (SSR), Form A, 0.5A @ 24VÅ(ac) minimum, 264VÅ(ac) maximum, opto-
isolated, without contact suppression
Electromechanical relay, Form C, 5A, 24 to 240VÅ(ac) or 30VÎ(dc) maximum, resistive load,
100,000 cycles at rated load
Electromechanical relay, Form A, 5A, 24 to 240VÅ(ac) or 30VÎ(dc) maximum, resistive load,
100,000 cycles at rated load
NO-ARC relay, Form A, 15A, 24 to 240VÅ(ac), no VÎ(dc), resistive load, 2 million cycles at
rated load
Universal process:
- 0 to 10VÎ(dc) into a minimum 1,000Ω load
- 4 to 20mA into maximum 800Ω load
Operator Interface
Dual 4 digit, 7 segment LED displays
Typical display update rate 1Hz
Advance, innity, up and down keys plus an EZ-KEY key (not available in 1⁄32 DIN)
A/M Key on 1/16 DIN package automatically programmed as an Auto/Manual transfer mode
function.
EZ1 Key on 1/8 and 1/4 DIN packages automatically programmed as an Auto/Manual transfer
mode function.