EZ-ZONE PM Limit Express 19 Operations Menu
Operations Menu
Display Parameter Name Description
Range
Defaults are shown bold
[`LL;S]
[ LL.S]
Limit Low Set Point
Set the low process value that will trig-
ger the limit.
Appears if: Limit sides set to low or both.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C
[`Lh;S]
[ Lh.S]
Limit High Set Point
Set the high process value that will trig-
ger the limit.
Appears if: Limit sides set to high or both.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C
[`A;Lo]
[ A.Lo]
Alarm Low Set Point
Process - set the process value that will
trigger a low alarm.
Appears if: Alarm Type (A.ty) is set to
Process Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 32.0°F or 0.0°C
[`A;hi]
[ A.hi]
Alarm High Set Point
Process - set the process value that will
trigger a high alarm.
Appears if: Alarm Type (A.ty) is set to
Process Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 300.0°F or 150.0°C
[`i;CA]
[ i.CA]
Calibration Offset
Set an offset value for a process output.
Appears if: Always
-1,999.000 to 9,999.000°F or units
-1,110.555 to 5,555.000°C
0.0