2-2
2.2 Control Capability
Number of Loops: 12, Dual Output.
Control Outputs: Cycle Time Proportioning, Distributed Zero Crossing, or On/Off;
all independently selectable for each loop.
Control Action: Reverse [heat] or Direct [cool], independently selectable for each
loop.
Digital Control Outputs: Nominal 5vdc at 10ma to driveoptically- isolated solid-state relays.
Cycle Time: Programmable foreach loop, 1-255 secs.
Output Resolution: 16 bits.
2.3 Digital Outputs
Number: 11
Configuration: 1 Global Alarm
9 for alarms or events.
1 not used standard PROM
2.4 Digital Inputs
Number: 9
Configuration: 8 for triggers
1 not used standard PROM
2.5 Serial Interface
Type: RS-232 or RS-485 4 wire, factory select
Isolation: RS-232: None.
RS-485: To RS-485 Specification.
Baud Rate: 2400 or 9600, menu selectable.
Protocol: Form of ANSI X3.28-1976, Compatible with Allen-Bradley PLC,
Half Duplex.
Error Check: BCC or CRC, menu selectable.
Number of Controllers: Each communications line: 32 with RS- 485, 1 with RS-232.
2.6 Power Supply